PRELIMINARY - NOT APPROVED FOR PROCUREMENT, FABRICATION, CONNECTION, POWERED TESTING, MOTION OR ENERGIZATION

The contactors are outside the robot.

A physical external panel candidate now feeds one touch-safe tether and exactly eight protected onboard bus-source inputs.

7native KiCad files: root plus six sheets
ERC 0 / 0connectivity and annotation only
2LC1D40ABD candidates
8protected bus-source feeds

The EDM hardware mismatch is corrected

K1 and K2 each use explicit 21-22 mirror-certified NC auxiliary contacts. Their three main poles are wired in series. This is still an unvalidated candidate circuit: no achieved Category, PL, SIL or permission to energize is claimed.

Fuse values are intentionally absent

Fault current, cable length, ambient temperature, bundling, inrush, duty cycle, regeneration, connector limits, coordination and jurisdiction are not yet closed. No fuse value or conductor is released.

Physical system map

External enclosure candidate

External panel STEP · Robot distributor STEP · KiCad project · eight-feed register · open holds

Native schematic sheets

01 · External mains boundary and DC sources
02 · Dual-channel E-stop, monitored manual reset and PNOZ s4
03 · Two series LC1D40ABD contactors and mirror-feedback loop
04 · SBS75G touch-safe three-contact tether
05 · Robot inlet, main boundary and eight protected bus-source feeds
06 · Status, telemetry and fail-closed commissioning boundary